Mitsubishi · Heat pump
P8 Pipe temperature out of range (coil not cooling or heating)
What the control is telling you
The coil temperature does not move far enough from room temperature: in cooling the coil must be at least 3°C below the return air, in heating at least 3°C above. It takes at least 9 minutes (cooling) or 27 minutes (heating) to detect. Not checked in dry mode or during defrost.
Applies to: PEAD-RP35/50/60/71/100/125/140JA and JA(L) ducted indoor units (220-240 V models)
Likely causes
- Low refrigerant charge
- Pipe sensor holder loose on the pipe
- Refrigerant circuit fault
- On multi-unit systems: line sets crossed between units
- On multi-unit systems: indoor/outdoor wires crossed between units
- Room or pipe sensor reading wrong
- Service valves not fully open
Test and repair steps
- Make sure both service valves on the outdoor unit are fully open.
- Check that the TH2 and TH5 sensors are clipped tightly to the pipe.
- Compare room and pipe temperatures on the remote (or with the outdoor A-Control service tool) with real readings.
- Check the refrigerant charge and look for leaks.
- On twin/triple or multiple systems, confirm each line set and S1-S2-S3 wire goes to the matching indoor unit.
- After the repair, cycle the power and run the unit to confirm the code does not come back.
Models that show this code
14 models in Mr. Slim PEAD-RP JA(L) ducted indoor unit
Other codes on the same units
- P2 Liquid pipe sensor TH2 open or shorted
- P4 Drain float switch disconnected
- P5 Drain overflow - float switch wet with pump running
- P6 Coil freeze or overheat protection
- P9 Coil sensor TH5 open or shorted
- Centrally Controlled indicator Operation prohibited by master controller
- FILTER Clean the filter indicator
- Fb Indoor control board memory error
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Mitsubishi Electric PEAD-RP35-140JA(L) Service Manual, 10-3 Self-diagnosis action table, p.32. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.