Midea · Mini-split
PC06 Discharge temperature protection
What the control is telling you
Discharge temperature stayed above 239 F (115 C) for 10 s; the compressor stops and restarts once it falls below 194 F (90 C). Outdoor board shows P4; 48K HH shows J2. The indoor manual lists a 226 F (108 C) / 9 s shutoff for its matched outdoor units.
Applies to: DLCM(R/H)B multi-zone outdoor units with DLFSHBH high wall indoor units (Midea, Carrier, Viessmann)
Likely causes
- Low charge / leak
- Bad discharge sensor
- Sensor wiring
- Bad outdoor PCB
Test and repair steps
- Safety kill power at the disconnect and wait for the inverter capacitors to discharge before touching boards or wiring.
- Confirm the discharge temperature really is high (over 239 F / 115 C) with a contact thermometer.
- Check the discharge sensor plug and wiring against the diagram, and measure the sensor (about 54.9 kOhm at 77 F).
- Check for a leak / low charge. Repair the leak and recharge.
- If charge and sensor are good, replace the outdoor main PCB.
Models that show this code
12 models in Midea DLCM(R/H)B multi-zone outdoor, Midea DLFSHBH wall indoor (DLCM multi-zone)
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Table 23 Outdoor Unit Error Display p.26; diagnosis p.66; Carrier MS-DLFSHB-01 High Wall Ductless Service Manual (04/2021), Table 9 p.17, safety features p.11. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.