Lennox · Air handler

E382 EIM relay W1 fault

High severity

What the control is telling you

EIM W1 relay energized but W1 input not sensed after three seconds (furnace or air handler modes). S30/S40 thermostat alert code 382 (shown as E382 on the unit control display).

Applies to: Lennox communicating air handlers and EIM-equipped indoor units in S30/S40 smart thermostat systems

Likely causes

  • Failed W1 relay
  • Wiring fault

Test and repair steps

  1. Check W1 wiring from the EIM.
  2. Replace the EIM if the relay fails.
  3. Clears when W1 relay input is sensed.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.28. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.