E115 Low secondary (24 VAC) voltage
What the control is telling you
24 VAC to a component control is below the required 18 to 30 VAC range. S30/S40 thermostat alert code 115 (shown as E115 on the unit control display).
Applies to: Lennox communicating air handlers and EIM-equipped indoor units in S30/S40 smart thermostat systems
Likely causes
- Overloaded transformer (power-robbing accessories)
- Low line voltage
- Loose wiring
Test and repair steps
- Measure 24 VAC at the control and correct it.
- Look for extra accessories loading the transformer.
- A larger or additional VA transformer may be needed.
- Damper module runs non-zone mode until voltage is restored.
- Clears automatically once fixed.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.16. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.