Lennox · Air handler

543 Zone 2 temperature sensor fault

Medium severity

What the control is telling you

Zone 2 sensor reading out of range or open/short for more than five seconds; zone shows '--', system runs central mode (all dampers open). Escalates after 10 minutes. Thermostat shows 'Problem (Zoning Control)'. S30/S40 thermostat alert code 543.

Applies to: Lennox communicating air handlers and EIM-equipped indoor units in S30/S40 smart thermostat systems

Likely causes

  • Loose or miswired sensor connections
  • Open or shorted sensor
  • Two sensors assigned the same zone number

Test and repair steps

  1. Check sensor and damper control module terminals for loose or incorrect wiring.
  2. Check zone number assignments; no two sensors may share a number.
  3. Replace the sensor if open or shorted.
  4. Clears 30 seconds after the condition ends.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.45. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.