Lennox · Air handler
532 Zoning pressure switch opened (high pressure)
What the control is telling you
Zoning pressure switch opened: compressor pressure above limit, compressor off; zoning restores when the switch closes (dealer information). S30/S40 thermostat alert code 532.
Applies to: Lennox communicating air handlers and EIM-equipped indoor units in S30/S40 smart thermostat systems
Likely causes
- High refrigerant pressure during zoning (low airflow)
- AC system without the switch
Test and repair steps
- Check airflow and bypass in zoned operation.
- On some AC systems, the fix is a jumper across the damper control module's pressure switch terminals.
- Clears when pressure is within limits.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.44. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.