Lennox · Air handler
34 Must program unit capacity for device
What the control is telling you
The indoor or outdoor control has no programmed unit capacity (tonnage/unit size). S30/S40 thermostat alert code 34.
Applies to: Lennox communicating air handlers and EIM-equipped indoor units in S30/S40 smart thermostat systems
Likely causes
- Replacement control not programmed with unit size code
Test and repair steps
- Remove thermostat power before programming the unit control.
- Program the unit capacity at the unit control per its installation instructions (unit size code).
- Reconnect the thermostat wires.
- S30 go to Menu > Settings > Advanced Settings, open View Dealer Control Center, then pick Equipment > Reset All Equipment. The thermostat will find every Lennox communicating device again.
- S40 go to Menu > Settings > Advanced Settings, open View Service Support Center, then Equipment Setting > Reset and pick Reset HVAC Equipment.
- Clears automatically once fixed.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.10. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.