Lennox · Air handler
31 Lost communication with device
What the control is telling you
A component (indoor, outdoor, EIM or damper control module) has not talked to the thermostat for more than three minutes. S30/S40 thermostat alert code 31.
Applies to: Lennox communicating air handlers and EIM-equipped indoor units in S30/S40 smart thermostat systems
Likely causes
- Loose or open communication/24 V wiring
- Float switch on air handler drain pan tripped (wired in series with R)
- Freezestat installed and open
Test and repair steps
- Check connections and voltages at the device.
- Ohm the wires for continuity.
- If a float switch is on the air handler drain pan, check for a clogged condensate line tripping it.
- Check whether a freezestat is installed and open.
- Cycle power if it persists; clears when communication returns.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.10. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.