Lennox · Air handler
20 Protocol upgrade required
What the control is telling you
Thermostat firmware is too old for one connected device. Update the firmware so they can talk. S30/S40 alert code 20.
Applies to: Lennox communicating air handlers and EIM-equipped indoor units in S30/S40 smart thermostat systems
Likely causes
- Thermostat firmware older than a connected device
Test and repair steps
- Update the thermostat firmware (Wi-Fi connection / auto update).
- Re-check that all devices are detected after the update.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.9. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.