Lennox · Air conditioner
E433 Inverter compressor over-current (inverter code 29)
What the control is telling you
Compressor peak phase current above 28 A (six-minute delay at startup). The inverter first slows down (code 14); if current stays high the unit stops. Five times in 60 minutes = lockout. The outdoor control can also trigger 433 if speed falls below minimum at startup. Inverter LED flash code 29 (red 2 flashes, green 9 flashes). S30/S40 thermostat alert code 433 (shown as E433 on the unit control display).
Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- High load or pressure
- Older outdoor control software
Test and repair steps
- If 433 occurs without inverter flash code 29, the outdoor control triggered it: check its software version in the thermostat outdoor unit diagnostics.
- Software 1.27 and later adds a 6-minute (cooling) and 11-minute (heating) delay; update over the internet with auto update on, or replace the outdoor control with catalog 17D27 or newer.
- Check for high pressure conditions.
- Clear by disconnecting power to both indoor and outdoor units, reconnect and restart.
- Check inverter LEDs flash code 29 = red 2 flashes, green 9 flashes. Normal inverter LEDs with no fault: red ON, green OFF.
Settings for these units
- Outdoor unit clearances · Lennox EL16KC1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.38. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.