Lennox · Air conditioner

E432 Inverter DC link high voltage (inverter code 28)

High severity

What the control is telling you

DC link capacitor voltage above 480 VDC; unit stops. 10 times in 60 minutes = lockout. Inverter LED flash code 28 (red 2 flashes, green 8 flashes). S30/S40 thermostat alert code 432 (shown as E432 on the unit control display).

Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems

Likely causes

  • High input voltage
  • Inverter fault
  • Compressor wiring or winding fault

Test and repair steps

  1. Check U, V, W connections at the inverter and compressor.
  2. Check compressor winding resistance and ground.
  3. Check input power single phase 208/230 VAC +10%.
  4. Check DC link and MICOM sensing voltage; replace inverter if out of range.
  5. Clear by disconnecting power to the outdoor unit and restarting.
  6. Check inverter LEDs flash code 28 = red 2 flashes, green 8 flashes. Normal inverter LEDs with no fault: red ON, green OFF.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.37. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.