KeepRite · Heat pump

32 Low pressure switch open

High severity KeepRite *SA/*SH Single-Stage CommunicatingKeepRite *CA/*CH Two-Stage Communicating

What the control is telling you

The low-pressure switch opened and the compressor was stopped.

Applies to: KeepRite *SA5/*SA6 AC and *SH4/*SH5/*SH6 HP single-stage communicating; *CA7/*CA9 AC and *CH6/*CH9 HP two-stage communicating

Likely causes

  • Low refrigerant charge
  • Low indoor airflow (cooling)
  • Outdoor fan or coil problem (heat pump heating)

Test and repair steps

  1. Check refrigerant charge and leak-check if low.
  2. Check indoor filter, blower and coil airflow in cooling.
  3. For a heat pump in heating, check outdoor fan and outdoor coil.

Models that show this code

11 models in KeepRite *SA/*SH Single-Stage Communicating, KeepRite *CA/*CH Two-Stage Communicating

*CH624*CH636*CH648*CH660*CH924*CH936*CH948*CH960*SH4*SH5*SH6

Other codes on the same units

  • 16 Lost communication with wall control
  • 25 Model plug missing or invalid
  • 31 High pressure switch open
  • 45 Outdoor control board failure
  • 46 Brown-out (low voltage)
  • 47 No 230 V at the unit
  • 53 Outdoor air temperature sensor fault
  • 55 Outdoor coil sensor fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: KeepRite/ICP C4A3/H4A3/T4A3/CXA6 Installation Instructions 421 01 5103 05, Table 1 Status Codes, p.17; KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Table 13 Status Codes (single-stage); KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Table 17 Troubleshooting (two-stage). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.