Status code recall (SW1-1) Read the last 7 stored status codes
What the display is showing
Turning setup switch SW1-1 ON and closing the blower door switch makes the amber LED flash up to seven stored status codes in order, followed by an eighth flash that is the heartbeat. Codes survive power loss. Turn SW1-1 back OFF afterwards.
Applies to: ICP (F/G)9MAE modulating furnaces
What to do
- No thermostat call may be present and all blower-off delays must be finished.
- Leave 115 V power on and remove the blower door.
- Turn setup switch SW1-1 ON and manually close the blower door switch.
- Watch the LED up to 7 codes flash, then a heartbeat.
- Turn SW1-1 OFF, release the door switch and refit the blower door.
Models that show this code
6 models in ICP (F/G)9MAE Modulating Furnace
Other codes on the same units
- 7 Limit circuit lockout
- 8 Gas heating lockout
- 9 Medium/high pressure switch or PSR relay did not close or reopened
- 10 Line voltage polarity
- Amber LED heartbeat Amber LED heartbeat - normal operation
- Component self-test (SW1-6) Furnace component self-test
- LED off Amber status LED off - no power / blown 3 A fuse
- LED steady ON Amber LED on solid - control lockout / wrong model plug
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: ICP (F/G)9MAE Service Manual 440 04 4700 00, Retrieving Stored Fault Codes, p.22. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.