ICP · Furnace

Component self-test (SW1-6) Furnace component self-test

Menu / mode display ICP (F/G)9MAE Modulating Furnace

What the display is showing

Setup switch SW1-6 starts a service self-test: inducer on at medium speed, gas valve communication check, igniter on for 15 seconds, then blower at mid airflow for 15 seconds, then the inducer stops. At the end the LED flashes a result: heartbeat, 2+5, 3+5, 4+1 or 4+2. To repeat, turn SW1-6 OFF then ON.

Applies to: ICP (F/G)9MAE modulating furnaces

What to do

  1. Remove the blower door and take the wire off the R terminal of the control board.
  2. Turn setup switch SW1-6 ON.
  3. Manually close the blower door switch and watch the test run.
  4. Release the door switch, reconnect the R wire and refit the blower door.

Models that show this code

6 models in ICP (F/G)9MAE Modulating Furnace

G9MAE0601714G9MAE0602120G9MAE0801714G9MAE0802120G9MAE1002122G9MAE1202422

Other codes on the same units

  • 7 Limit circuit lockout
  • 8 Gas heating lockout
  • 9 Medium/high pressure switch or PSR relay did not close or reopened
  • 10 Line voltage polarity
  • Amber LED heartbeat Amber LED heartbeat - normal operation
  • LED off Amber status LED off - no power / blown 3 A fuse
  • LED steady ON Amber LED on solid - control lockout / wrong model plug
  • Status code recall (SW1-1) Read the last 7 stored status codes

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: ICP (F/G)9MAE Service Manual 440 04 4700 00, Component Self-Test, p.22. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.