Gree · Heat pump

H0 Compressor slowed - high indoor coil temp in heating

Low severity Gree Sapphire

What the control is telling you

Normal operation continues with compressor speed cut because the indoor coil is too hot in heating.

Applies to: Gree Sapphire 9-24k (SAP..HP230V1A)

Likely causes

  • Dirty filter or low indoor airflow
  • Overcharge

Test and repair steps

  1. Clean the filter and raise fan speed.
  2. Check the charge.

Models that show this code

4 models in Gree Sapphire

SAP09HP230V1AHSAP12HP230V1AHSAP18HP230V1AHSAP24HP230V1AH

Other codes on the same units

  • F4 Outdoor coil (condenser middle) sensor open or shorted
  • F5 Compressor discharge sensor open or shorted
  • F6 Compressor slowed - overload
  • F8 Compressor slowed - high current
  • F9 Compressor slowed - high discharge temperature
  • H3 Compressor overload protection
  • H4 System abnormal (overload)
  • H5 IPM (inverter module) protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Gree Sapphire 9-12k (SAP09-12HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Sapphire 18-24k (SAP18-24HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.