Fujitsu · Heat pump
Outdoor LED3 6 flashes 3-way valve sensor error, unit C (24 type) (outdoor board LED)
What the control is telling you
Multi-zone 18/24 outdoor board: LED3 flashes 6 times while the other LEDs stay off. Same fault family as indoor code 76. The LEDs sit on the back side of the board and are seen through a hole.
Applies to: Fujitsu 18 type (2-zone) and 24 type (3-zone) multi outdoor units
Likely causes
- Plug
- Thermistor
- PCB
Test and repair steps
- Look at the outdoor PCB LEDs (rear of the board, viewed through the hole) and count the flashes on each LED.
- Then follow the checks for indoor code 76: Check the sensor plug on the board is seated and on the right connector, and the lead is not cut or pinched.
- Unplug the thermistor and measure its resistance; compare with the resistance/temperature chart in the service manual. Open or shorted = replace.
- With the plug connected, check for about DC 5.0 V across the thermistor terminals on the board; no voltage = board fault.
Settings for these units
Operating range and service space · Fujitsu multi-zone outdoor 18/24 type
| Item | Value |
|---|---|
| Cooling outdoor range | 14 to 115 F DB |
| Heating outdoor range | 5 to 75 F DB |
| Cooling indoor range | 65 to 90 F DB |
| Heating indoor range | 60 to 88 F DB |
| Rear (open top, rear wall only) | 4 in. or more |
| Rear + sides | 4 in. rear, 10 in. sides |
| Front wall only | 24 in. or more |
| Between side-by-side units | 10 in. or more |
| Base height | 2 in. or more above floor |
Unit tilt no more than 3 degrees and never toward the compressor side.
Below 32 F outdoor do not fit the drain pipe/caps (freezing).
Other codes on the same units
- Outdoor LED1 7 flashes Compressor temperature sensor error (outdoor board LED)
- Outdoor LED1 8 flashes Heat sink temperature sensor error (outdoor board LED)
- Outdoor LED1 9 flashes High pressure switch 1 error (outdoor board LED)
- Outdoor LED2 1 flash Serial comms error, outdoor to indoor unit B (outdoor board LED)
- Outdoor LED2 5 flashes 2-way valve sensor error, unit B (outdoor board LED)
- Outdoor LED2 6 flashes 3-way valve sensor error, unit B (outdoor board LED)
- Outdoor LED3 1 flash Serial comms error, outdoor to indoor unit C (24 type) (outdoor board LED)
- Outdoor LED3 5 flashes 2-way valve sensor error, unit C (24 type) (outdoor board LED)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Fujitsu Outdoor unit 18-24 type (North American trilingual) installation P-N 9374747160.pdf - section 8.2 Outdoor unit LED. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.