Fujitsu · Heat pump

Outdoor LED3 1 flash Serial comms error, outdoor to indoor unit C (24 type) (outdoor board LED)

High severity Fujitsu multi-zone outdoor 18/24 type

What the control is telling you

Multi-zone 18/24 outdoor board: LED3 flashes 1 time while the other LEDs stay off. Same fault family as indoor code 11. The LEDs sit on the back side of the board and are seen through a hole.

Applies to: Fujitsu 18 type (2-zone) and 24 type (3-zone) multi outdoor units

Likely causes

  • Loose, wrong or broken wire on terminals 1-2-3
  • Supply voltage out of range
  • Electrical noise / poor ground
  • Indoor or outdoor main PCB failure
  • Outdoor or indoor fan motor dragging down the circuit

Test and repair steps

  1. Look at the outdoor PCB LEDs (rear of the board, viewed through the hole) and count the flashes on each LED.
  2. Then follow the checks for indoor code 11: Reset power and run; if it does not return, check for outside causes (ground, noise sources near the cable).
  3. Check the 1-2-3 connection cable at both units for loose screws, swapped wires or damage; correct per the install manual.
  4. Check supply voltage at the outdoor terminal block (NA units: 208/230 V, keep within 187-253 V).

Settings for these units

Operating range and service space · Fujitsu multi-zone outdoor 18/24 type

ItemValue
Cooling outdoor range14 to 115 F DB
Heating outdoor range5 to 75 F DB
Cooling indoor range65 to 90 F DB
Heating indoor range60 to 88 F DB
Rear (open top, rear wall only)4 in. or more
Rear + sides4 in. rear, 10 in. sides
Front wall only24 in. or more
Between side-by-side units10 in. or more
Base height2 in. or more above floor

Unit tilt no more than 3 degrees and never toward the compressor side.

Below 32 F outdoor do not fit the drain pipe/caps (freezing).

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Fujitsu Outdoor unit 18-24 type (North American trilingual) installation P-N 9374747160.pdf - section 8.2 Outdoor unit LED. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.