Fujitsu · Heat pump
74 Outdoor air temperature sensor error
What the control is telling you
Outdoor ambient thermistor reads open or shorted. Indoor lamps: OPERATION (green) flashes 7x, TIMER (orange) flashes 4x, ECONOMY (green) flashes fast nonstop; wired remote shows 74.
Applies to: Fujitsu ductless heat pumps: Fujitsu ductless split/multi/VRF (general code list), Fujitsu wall-mounted 7-15 (NA ASU/AOU type), Fujitsu slim duct ARU 7-18 (LL type)
Likely causes
- Plug
- Thermistor
- PCB
Test and repair steps
- Check the sensor plug on the board is seated and on the right connector, and the lead is not cut or pinched.
- Unplug the thermistor and measure its resistance; compare with the resistance/temperature chart in the service manual. Open or shorted = replace.
- With the plug connected, check for about DC 5.0 V across the thermistor terminals on the board; no voltage = board fault.
- Cycle power after any repair and confirm the code does not return.
Settings for these units
- Operating range and service space · Fujitsu multi-zone outdoor 18/24 type
Other codes on the same units
- 68 Rush current limiting resistor temp rise error
- 71 Discharge temperature sensor error
- 72 Compressor temperature sensor error
- 73 Outdoor coil liquid temperature sensor error
- 75 Suction gas temperature sensor error
- 76 2-way / 3-way valve temperature sensor error
- 77 Heat sink temperature sensor error
- 82 Sub-cool heat exchanger sensor error
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Fujitsu All Fujitsu split - multi - VRF (generic code list) codes.pdf - section error code table (indoor LED flashes); Fujitsu Wall-mounted 7-9-12-15 (North American trilingual, UTY-RNNUM remotes; e.g. ASU9-12-15 RLF1-RLS familie.pdf - section 14 Error codes; Fujitsu Slim duct AR07-09-12-14-18 (ARU-ARYG LL-type equivalent) installation P-N 9381858064.pdf - section 14 Error codes. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.