Fujitsu · Heat pump

68 Rush current limiting resistor temp rise error

Medium severity Fujitsu wall-mounted 7-15 (NA ASU/AOU type)Fujitsu slim duct ARU 7-18 (LL type)

What the control is telling you

The inrush limiting resistor in the outdoor unit overheated. Indoor lamps: OPERATION (green) flashes 6x, TIMER (orange) flashes 8x, ECONOMY (green) flashes fast nonstop; wired remote shows 68.

Applies to: Fujitsu ductless heat pumps: Fujitsu wall-mounted 7-15 (NA ASU/AOU type), Fujitsu slim duct ARU 7-18 (LL type)

Likely causes

  • Frequent power cycling
  • Board fault

Test and repair steps

  1. Avoid rapid power on/off.
  2. Check supply; replace the outdoor PCB if repeated.

Settings for these units

Other codes on the same units

  • 62 Outdoor main PCB error (EEPROM / model / micro comms)
  • 63 Inverter error
  • 64 PFC / active filter circuit error
  • 65 IPM / trip terminal L error
  • 71 Discharge temperature sensor error
  • 72 Compressor temperature sensor error
  • 73 Outdoor coil liquid temperature sensor error
  • 74 Outdoor air temperature sensor error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Fujitsu Wall-mounted 7-9-12-15 (North American trilingual, UTY-RNNUM remotes; e.g. ASU9-12-15 RLF1-RLS familie.pdf - section 14 Error codes; Fujitsu Slim duct AR07-09-12-14-18 (ARU-ARYG LL-type equivalent) installation P-N 9381858064.pdf - section 14 Error codes. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.