Fujitsu · Heat pump

35 MANUAL AUTO button error

Low severity Fujitsu ductless split/multi/VRF (general code list)Fujitsu wall-mounted 7-15 (NA ASU/AOU type)Fujitsu slim duct ARU 7-18 (LL type)

What the control is telling you

Indoor board sees the MANUAL AUTO push-button held in continuously for 60 s or longer. Indoor lamps: OPERATION (green) flashes 3x, TIMER (orange) flashes 5x, ECONOMY (green) flashes fast nonstop; wired remote shows 35.

Applies to: Fujitsu ductless heat pumps: Fujitsu ductless split/multi/VRF (general code list), Fujitsu wall-mounted 7-15 (NA ASU/AOU type), Fujitsu slim duct ARU 7-18 (LL type)

Likely causes

  • Button stuck or shorted
  • Indicator / controller PCB fault

Test and repair steps

  1. Check the button is not jammed by the front panel.
  2. Check it opens and closes with a meter; replace if it does not switch.
  3. If the button is fine, replace the main PCB and indicator PCB.

Settings for these units

Other codes on the same units

  • 29 Connection unit number error (wired remote system)
  • 31 Power supply interruption error
  • 32 Indoor main PCB error (EEPROM / model info)
  • 33 Indoor fan motor power consumption error
  • 39 Indoor fan motor power supply error
  • 41 Room (intake air) temperature sensor error
  • 42 Indoor coil (heat exchanger middle) sensor error
  • 44 Human (occupancy) sensor error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Fujitsu All Fujitsu split - multi - VRF (generic code list) codes.pdf - section error code table (indoor LED flashes); Fujitsu Wall-mounted 7-9-12-15 (North American trilingual, UTY-RNNUM remotes; e.g. ASU9-12-15 RLF1-RLS familie.pdf - section 14 Error codes; Fujitsu Wall-mounted KMCG (ASEH-AOEH 07-14) - Fujitsu UK; same error-code scheme as NA ASU-AOU units service S.pdf - section 3 Troubleshooting, 2 Troubleshooting with error code; Fujitsu Slim duct AR07-09-12-14-18 (ARU-ARYG LL-type equivalent) installation P-N 9381858064.pdf - section 14 Error codes. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.