Daikin · Air conditioner

Red comm LED 1 flash Network: communications failure

Medium severity Daikin FIT DC6VS/DC9VSA

What the control is telling you

Red communications LED (outdoor board H1P, indoor board H2P) flashes once: the control got a packet it does not know, or lost communication.

Applies to: DC6VS***1*A*, DC9VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)

Likely causes

  • Unknown packet received
  • Communication failure

Test and repair steps

  1. Press the LEARN button about 5 seconds to reset the network.
  2. Check the communication wiring connections.

Models that show this code

10 models in Daikin FIT DC6VS/DC9VSA

DC6VS*181DC6VS*241DC6VS*301DC6VS*361DC6VS*421DC6VS*481DC6VS*601DC9VSA2410DC9VSA3610DC9VSA4810

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin 3P761829-1B FIT outdoor unit installation & service reference, Network Troubleshooting p.47 (printed page). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.