Daikin · Air conditioner

Ed1 Bad shared or network data

High severity Daikin FIT DC6VS/DC9VSA

What the control is telling you

Thermostat shows D1, outdoor board display shows Ed1. The unit is wired as a communicating system but the shared data or network data on the control is not valid.

Applies to: DC6VS***1*A*, DC9VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)

Likely causes

  • Invalid shared data or network data

Test and repair steps

  1. Replace the control board if needed.

Models that show this code

10 models in Daikin FIT DC6VS/DC9VSA

DC6VS*181DC6VS*241DC6VS*301DC6VS*361DC6VS*421DC6VS*481DC6VS*601DC9VSA2410DC9VSA3610DC9VSA4810

Other codes on the same units

  • E56 Suction temperature sensor out of range
  • E58 Compressor overload (OL) sensor open
  • Eb0 Indoor airflow near zero
  • Eb9 Indoor airflow below what is needed
  • Ed0 No shared data on the control
  • Ed2 Airflow needed is more than the indoor unit can give
  • Ed3 Shared data does not match the hardware
  • Ed4 Memory card data rejected

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.46 (printed page). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.