Carrier · Mini-split
PC30 High pressure protection
What the control is telling you
The high-pressure switch opened. Outdoor board shows P1; 48K HH shows J5.
Applies to: DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)
Likely causes
- Loose switch wiring
- Bad switch
- High outdoor temperature
- Poor outdoor airflow / dirty coil
- Overcharge or restriction
- Bad outdoor PCB
Test and repair steps
- Safety kill power at the disconnect and wait for the inverter capacitors to discharge before touching boards or wiring.
- Check the high-pressure switch wiring to the main board.
- Unplug the switch and measure it. A good switch reads 0 ohms at rest; open = replace it.
- If outdoor air is above 122 F (50 C), the unit is outside its range: shut it down.
- Check outdoor airflow nothing blocking the coil, coil clean, outdoor fan running (see EC07 if not).
- Check the refrigerant side (overcharge, restriction). If everything checks out, replace the outdoor main board.
Models that show this code
7 models in Carrier DLCM(R/H)B multi-zone outdoor
Other codes on the same units
- PC06 Discharge temperature protection
- PC08 Outdoor over-current protection
- PC10 Low AC supply voltage
- PC11 AC supply voltage protection (over voltage)
- PC12 DC bus high voltage / 341 MCE error
- PC31 Low pressure protection
- PC40 Main chip to compressor drive chip communication error
- PC42 Compressor start failure
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Table 23 Outdoor Unit Error Display p.26; diagnosis p.60-61. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.