Carrier · Mini-split
ODU P1 High pressure protection (outdoor board)
What the control is telling you
Outdoor board display. Indoor shows PC30 (old P6).
Applies to: DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)
Test and repair steps
- Safety kill power at the disconnect and wait for the inverter capacitors to discharge before touching boards or wiring.
- Check the high-pressure switch wiring to the main board.
- Unplug the switch and measure it. A good switch reads 0 ohms at rest; open = replace it.
- If outdoor air is above 122 F (50 C), the unit is outside its range: shut it down.
- Check outdoor airflow nothing blocking the coil, coil clean, outdoor fan running (see EC07 if not).
- Check the refrigerant side (overcharge, restriction). If everything checks out, replace the outdoor main board.
Models that show this code
7 models in Carrier DLCM(R/H)B multi-zone outdoor
Other codes on the same units
- ODU Hz readout Compressor running frequency
- ODU LC Low ambient cooling mode
- ODU LP Low outdoor temperature protection (outdoor board)
- ODU P0 Compressor top overheat (outdoor board)
- ODU P2 Low pressure protection (outdoor board)
- ODU P3 Current overload (outdoor board)
- ODU P4 Discharge temperature protection (outdoor board)
- ODU P5 Condenser high temperature (outdoor board)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Table 27 Outdoor Unit Digital Codes p.32; diagnosis p.60-61. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.