EH66 Evaporator coil inlet temperature sensor (T2B) open or short circuit
What the control is telling you
Listed together with EH62 for the T2B sensor. The T2B sensor is open or shorted.
Applies to: D5FSOAH indoor unit
Test and repair steps
- Disconnect the sensor from the PCB.
- Measure the sensor resistance with a multimeter.
- Compare it with the resistance table in the appendix (p. 64).
- Check the sensor wiring and connections to the PCB.
- Replace the sensor if its resistance is out of range.
- If the sensor and wiring are good, replace the indoor PCB.
Models that show this code
3 models in D5FSOA
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: D5FSOAH service manual, p. 26, 32. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.