EH62 Evaporator coil inlet temperature sensor (T2B) open or short circuit

Medium severity D5FSOA

What the control is telling you

The T2B sensor is open or shorted.

Applies to: D5FSOAH indoor unit

Test and repair steps

  1. Disconnect the sensor from the PCB.
  2. Measure the sensor resistance with a multimeter.
  3. Compare it with the resistance table in the appendix (p. 64).
  4. Check the sensor wiring and connections to the PCB.
  5. Replace the sensor if its resistance is out of range.
  6. If the sensor and wiring are good, replace the indoor PCB.

Models that show this code

3 models in D5FSOA

D5FSOAH06XAKD5FSOAH12XAKD5FSOAH18XAK

Other codes on the same units

  • EH66 Evaporator coil inlet temperature sensor (T2B) open or short circuit
  • EHC1 Refrigerant sensor detects leakage
  • EHC2 Refrigerant sensor out of range with leakage detected
  • EHC3 Refrigerant sensor out of range
  • FHCC Refrigerant sensor error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: D5FSOAH service manual, p. 26, 32. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.