Carrier · Mini-split
EH03 Indoor fan speed out of range
What the control is telling you
Indoor fan stays too slow (about 300 RPM) or too fast (about 1500 RPM) long enough to stop the unit.
Applies to: DLFSHBH high wall indoor units 09-24K (Midea / Carrier / Viessmann) on DLC multi-zone or single-zone outdoor units
Likely causes
- Wiring
- Fan wheel blocked
- Bad fan motor
- Bad indoor PCB
Test and repair steps
- Safety kill power at the disconnect and wait for the inverter capacitors to discharge before touching boards or wiring.
- Restart after 2 minutes. If it clears, the unit is fine.
- With power off, turn the blower wheel by hand and clear anything that drags.
- Check the motor wiring.
- In standby measure at the motor plug pin 1 to 3 = 192-380 V DC on 208-230 V units (140-190 V on 115 V units); pin 4 to 3 = 13.5-16.5 V; pin 5 = 0-6.5 V; pin 6 = 13.5-16.5 V.
- Voltages wrong = replace the indoor PCB. Voltages right = replace the fan motor.
Models that show this code
5 models in Carrier DLFSHB high wall indoor
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier MS-DLFSHB-01 High Wall Ductless Service Manual (04/2021), Table 9 p.17, p.28-29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.