EH02 Zero-crossing signal error

Medium severity Carrier DLFSHB high wall indoor

What the control is telling you

The indoor board does not see the AC zero-crossing signal (none for 4 minutes or the timing is off).

Applies to: DLFSHBH high wall indoor units 09-24K (Midea / Carrier / Viessmann) on DLC multi-zone or single-zone outdoor units

Likely causes

  • Wiring / supply problem
  • Bad indoor PCB

Test and repair steps

  1. Safety kill power at the disconnect and wait for the inverter capacitors to discharge before touching boards or wiring.
  2. Check the power wiring and supply voltage. Fix and restart.
  3. If supply and wiring are good, replace the indoor main PCB.

Models that show this code

5 models in Carrier DLFSHB high wall indoor

DLFSHBH09XAKDLFSHBH12XAJDLFSHBH12XAKDLFSHBH18XAKDLFSHBH24XAK

Other codes on the same units

  • EC56 Indoor coil outlet sensor (T2B) fault
  • EH00 Indoor EEPROM error
  • EH0A Indoor EEPROM error
  • EH0b Indoor PCB to display board communication error
  • EH03 Indoor fan speed out of range
  • EH30 Indoor external fan low voltage
  • EH31 Indoor external fan over voltage
  • Eh60 Room sensor (T1) fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier MS-DLFSHB-01 High Wall Ductless Service Manual (04/2021), Table 9 p.17; DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024) p.37. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.