Carrier · Mini-split

EC72 Outdoor fan motor phase loss

High severity Carrier DLCM(R/H)B multi-zone outdoor

What the control is telling you

One phase of the outdoor DC fan output is missing.

Applies to: DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)

Likely causes

  • Loose fan lead
  • Bad fan motor winding
  • Bad outdoor PCB

Test and repair steps

  1. Safety kill power at the disconnect and wait for the inverter capacitors to discharge before touching boards or wiring.
  2. Restart after 2 minutes. If it clears, the unit is fine.
  3. Check the fan motor plug and leads.
  4. Check the three fan outputs for an obvious open.
  5. Measure the three fan windings. Unequal = replace the fan motor. Equal = replace the main PCB.

Models that show this code

7 models in Carrier DLCM(R/H)B multi-zone outdoor

DLCMHBH24CAKDLCMHBH30DAKDLCMHBH36DAKDLCMHBH48EAKDLCMRBH18BAKDLCMRBH36DAKDLCMRBH48EAK

Other codes on the same units

  • EC51 Outdoor EEPROM error
  • EC52 Condenser coil sensor (T3) fault
  • EC53 Outdoor ambient sensor (T4) fault
  • EC54 Discharge temperature sensor (TP/T5) fault
  • EC55 IPM temperature sensor fault
  • EC56 Indoor coil outlet sensor (T2B) fault
  • EC57 Refrigerant pipe sensor fault
  • EC71 Outdoor fan motor over-current

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Table 23 Outdoor Unit Error Display p.26; diagnosis p.70. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.