Carrier · Heat pump

71 Compressor dropped out

Medium severity Carrier Infinity 18VS 25VNA8Carrier 2-stage 24ANB/25HNB

What the control is telling you

Amber STATUS light flashes 71. The inverter reports the compressor is not running. Type: Event; reset: 6 minutes.

Applies to: Carrier Infinity 18VS variable speed heat pump 25VNA8 (AOC control + inverter)

Likely causes

  • Compressor stopped unexpectedly
  • 3-ton inverter in test mode (old software)

Test and repair steps

  1. See Carrier technical bulletin TIC 2015-0017.
  2. Replace a 3-ton inverter that entered test mode with one that has current software.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier 25VNA8 / 24VNA9 Service Manual, Table 6 Fault Code Actions, p.21. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.