Carrier · Air handler

EH 0E Water level switch overflow

High severity D5FUHA

What the control is telling you

The field-supplied water level float switch on CN23 has opened, which means an overflow. The system is signalled to shut off.

Applies to: D5FUHA indoor air handler with water level switch enabled

Likely causes

  • Condensate or water overflow in the drain pan
  • Float switch open or wiring fault

Test and repair steps

  1. Check the drain pan and drain line for water and clear any blockage.
  2. Check the float switch and its wiring at CN23.
  3. Confirm the switch contacts are closed in normal condition.
  4. If J7 is not removed, the switch input is not active; check this if the switch is in use.

Models that show this code

9 models in D5FUHA

D5FUHAH24AAKD5FUHAH36AAKD5FUHAH60AAKEHKMD05KNEHKMD08KNEHKMD10KNEHKMD15KNEHKMD20KNEHKMD25KN

Other codes on the same units

  • CP Remote switch off, unit blocked
  • FHCC Refrigerant sensor malfunction

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: D5FUHA service manual, p. 10. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.