EH 0E Water level switch overflow
What the control is telling you
The field-supplied water level float switch on CN23 has opened, which means an overflow. The system is signalled to shut off.
Applies to: D5FUHA indoor air handler with water level switch enabled
Likely causes
- Condensate or water overflow in the drain pan
- Float switch open or wiring fault
Test and repair steps
- Check the drain pan and drain line for water and clear any blockage.
- Check the float switch and its wiring at CN23.
- Confirm the switch contacts are closed in normal condition.
- If J7 is not removed, the switch input is not active; check this if the switch is in use.
Models that show this code
9 models in D5FUHA
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: D5FUHA service manual, p. 10. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.