Bosch · Tankless water heater

A9 Output power too low

Medium severity Bosch Greentherm T9800 SEBosch Greentherm T9900 SE

What the control is telling you

The unit is not reaching the required output power.

Applies to: Bosch Greentherm T9800 SE 160/199 and T9900 SE 160/199 / i 199 tankless water heaters

Likely causes

  • Low gas inlet pressure
  • Water sensor or flow sensor wiring problem

Test and repair steps

  1. Check gas inlet pressure.
  2. Check the three water temperature sensors and the flow sensor connections.
  3. Test or replace any sensor outside specification (see the resistance charts).

Models that show this code

6 models in Bosch Greentherm T9800 SE, Bosch Greentherm T9900 SE

Greentherm T9800 SE 160Greentherm T9800 SE 199Greentherm T9800 SEC 199Greentherm T9900 SE 160Greentherm T9900 SE 199Greentherm T9900 i 199

Other codes on the same units

  • A5 Condensing unit flue temperature sensor fault
  • A6 Inlet cold water temperature sensor fault
  • A7 Heat exchanger hot water temperature sensor fault
  • A8 Outlet hot water temperature sensor fault
  • C1 Flue blockage at start-up
  • C2 Flue blockage at start-up
  • C3 Flow sensor sees no recirculation
  • C5 Bypass water valve fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Bosch Greentherm T9800 SE 160/199 installation 6720816815 (06.2023), Table 24 Error code diagnostics, p.65-69; Bosch Greentherm T9900 SE 160/199 | i 199 installation 6 720 813 635 (2024-06), section 9.1 Error code diagnostics, p.68-73. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.