Allied · Furnace
8 flashes Lockout - too many flame dropouts
What the control is telling you
The flame lit then dropped out too many times in one heat call and the control locked out. Code listed only in the manual; no causes or steps given.
Applies to: A95UH, A93UH, 95G1UH, 92G1UH (sizes 045-08 to 135-20)
Test and repair steps
- Turn off power at the disconnect before touching wiring or components. Gas work: qualified gas tech only.
Models that show this code
15 models in A95/A93/95G1/92G1UH, A95/95G1UH, A93/92G1UH
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Allied 506724-01 (Issue 1108) A95UH/A93UH/95G1UH/92G1UH Installation Instructions, Diagnostic Codes p.53. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.