14 Ignition lockout
What the control is telling you
The furnace failed to ignite after the allowed number of tries.
Applies to: Carrier/ICP-family two-digit status codes — confirm with the code label on the unit
Likely causes
- Gas supply off / low pressure
- Dirty flame sensor
- Faulty igniter
- Gas valve not opening
- Poor ground
Test and repair steps
- Confirm gas supply and inlet pressure
- Clean the flame sensor and check microamps
- Check the hot surface igniter resistance / glow
- Verify 24V to gas valve during trial for ignition
- Check burner ground connection
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier/ICP status code label — verify per model. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.