York · technician tips
York service menus, test modes and resets
1 tips for furnace: access codes, button combinations, test modes and the resets you need at the appliance.
Jump to: Service & test modes (1)
Service & test modes
Forced fan, low and high fire, test and diagnostic modes, error history and live data.
Read or clear stored fault codes with the LAST ERROR button
Furnace · York UTEC IFC furnaces, York White-Rodgers IFC furnaces, York TM9V
The board keeps up to five fault codes, newest first, through power loss. Solid-LED errors are not stored. Retrieval only works with no thermostat signal active.
- End any heating, cooling or continuous-fan call
- Press and release LAST ERROR (more than 1/5 s, under 5 s); the LED flashes the stored codes, most recent first, with a 2 second pause between
- TM9V: after the codes it returns to slow green flash after a 5 second pause; press again to repeat
- Two green flashes = nothing stored
- To clear, hold the button 5 seconds or more; three green flashes confirm
Applies to: York IFC boards with LAST ERROR button
Source: York service letter ST-028-07 White Rodgers/Emerson IFC boards, Fault Code Sheet, p.5-7; York service tip ST-045-09 UTEC IFC boards, Fault Code Sheet; York TM9V installation manual 1083294-UIM-A-0114, Fault Code Storage and Retrieval, p.42. Written in our own words; check the manual for your exact model.
Related
Same tips in your pocket
The HVACopedia app has these tips, every error code and the settings tables offline.
For licensed technicians. Installer menus, test modes and access codes change settings that affect safety; only use them if you are trained on the appliance and understand the result. Gas, electrical and refrigerant work must be done by a qualified, licensed person, and the manufacturer’s manual for the exact model and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.