SIT · Gas fireplace · Ignition

NOVA 820 millivolt start-up and flame proving

820 NOVA millivolt

What happens, in order

  1. Bleed air from the gas lines and confirm inlet pressure is within the appliance maker's range
  2. Thermocouple and thermo-generator fully inserted; thermocouple hand-tight plus a quarter turn
  3. Wire the thermo-generator to the TPTH and TP terminals, and thermostat or wall switch to TPTH and TH
  4. Turn the knob to PILOT, press it, and light the pilot with a match or piezo igniter
  5. Keep holding until enough current builds to engage the safety magnet
  6. After about 3 minutes with only the thermo-generator connected, open-circuit voltage should be 500-750 mV; trim the pilot screw if outside range
  7. With a jumper from TPTH to TH, closed-circuit voltage should stay above 300 mV; with thermostat wires connected it should stay above 175 mV
  8. Turn the knob to ON and the main burner lights; cycle the thermostat and switch to check them
  9. Turning the knob to OFF puts out both the pilot and the main burner
  10. Safety interlock after OFF the pilot cannot be relit until the thermocouple has cooled (30 s or less)

Timings and thresholds

ItemValue
Thermo-generator open circuit500-750 mV
Closed circuit (jumper)Above 300 mV
Closed circuit (with thermostat)Above 175 mV
Pilot burn before readingAbout 3 min
Thermocouple open circuit (MV Plus)18-28 mV, replace under 14 mV

Applies to: SIT 820 NOVA millivolt, MV Plus vented and un-vented valves

Models

820 NOVA

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SIT 820 NOVA millivolt troubleshooting guide (fido-manual_1453404727), set-up and system checks. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.