Proflame · Gas fireplace · Ignition

Proflame IPI/CPI pilot ignition and flame proving

584 DFCGT

What happens, in order

  1. Remote or switch calls for flame; the DFC board starts pilot ignition and sparks at the pilot hood
  2. Pilot valve (EV1) opens; the pilot lights and the sense electrode must be engulfed to prove flame
  3. Once flame is proven, EV2 (main valve) is driven: expect a spike of about 5 V DC for about 2 s, then about 0.6 V DC continuous
  4. Main burner lights from the pilot and modulates on the 885 (electronic) or 886 (manual HI/LO) valve
  5. If no flame is proven, the board locks out and must be reset using the unlock sequence in the DFC instructions
  6. Spark continuing with the pilot lit points to the sense cable/electrode or DFC board
  7. OFF command with the IPI/CPI switch on CPI the pilot stays lit; on IPI the pilot should go out

Timings and thresholds

ItemValue
EV2 voltage after flame provenAbout 5 V DC for 2 s, then 0.6 V DC
DFC battery supply4.4-6.4 V DC (cells above 1.1 V each)
DFC AC/DC adapter supply6.7-7.3 V DC
DFC from fan control module6.0-6.4 V DC

Applies to: Proflame 880/885/886 gas valve with 584 DFC and GT remote systems

Models

Proflame 880885886

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Proflame system troubleshooting guide A10 (Troubleshooting flow charts, sections 5 and 6). Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.