Maxitrol · Gas fireplace · Ignition

GV60 remote-controlled valve startup

GV60

What happens, in order

  1. User presses Up-flame and Off together; the handset goes to manual mode
  2. Motor moves the valve to the pilot-only position and ratchets to prove the micro switch
  3. About 5 mV from the battery supply is applied to the gas valve magnet
  4. Solenoid pulls in on the magnet (audible clunk) and pilot gas flows
  5. Igniter sparks, the pilot lights and the thermocouple proves flame
  6. Relay in the receiver switches the magnet supply from batteries to the thermocouple
  7. Motor turns the valve to high flame

Timings and thresholds

ItemValue
Battery box minimum5.8 V DC
Thermocouple closed circuit10-15 mV
Magnet pull-in5 mV or more
Magnet drop-outAbout 2 mV
Drop-out time (good / bad)Over 20 s / under 10 s
Manual light pilot hold10 s

Applies to: Maxitrol GV60 remote control systems on fireplaces

Models

GV60

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: 10 Important Technical Tests for the Maxitrol GV60 system (fido-manual_1529953034), GV60 Startup Sequence. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.