Leak test, vacuum & equipment limits

Test pressures, vacuum targets, gauge ratings and recovery rules.

Pressure and leak testing

TestPressure / limit
Start looking for a leak with refrigerant5 to 30 psig through the system
Nitrogen strength / tightness test30 to 100 psig first, hold 1 hour. Then 170 psig, hold up to 24 hours with no drop
Nameplate test pressure unknownDo not go above 170 psig with nitrogen or CO₂
Regulator relief valve on the nitrogen bottleSet to open at 180 psig
R-134a systemsUnder 170 psig on both sides is enough
Trace gas mixAbout 10% refrigerant and 90% nitrogen, up to the unit's condensing pressure
Refrigerant-only test15 to 30 psig, then up to the manufacturer's high-side pressure
Nitrogen with trace refrigerant after a compressor swap (domestic)About 25 psig, then hold a vacuum for at least 1 hour: any rise is a leak
Epoxy repairTest at 5 psig, then at 100 psig
Valve adapter or saddle valveTest at 15 to 20 psig of refrigerant
Nitrogen flowing while brazing1 to 2 psi

Vacuum targets

ItemValue
Ready to charge500 microns or lower
Deep vacuum target250 microns, then isolate and watch for 1 to 3 minutes
Triple evacuationAbout 1,500 microns three times, breaking each with dry nitrogen to 0 to 3 psig
A reading that stalls near5,000 microns means water or ice in the system
Pump aloneShould reach 500 microns or lower on a tee. Dirty or white foamy oil means water
Hose sizeA 1/4 inch hose can take up to 8 times longer than a 1/2 inch hose

Gauges and cylinders

Take it with you

All of these tables, plus the calculators, are in the HVACopedia app, offline.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.