Fridge, freezer & room A/C data

Normal readings, drier and cap tube sizes, bench-test temperatures.

Domestic refrigerator operating readings (70 °F room)

ReadingStart of cycleMiddleEnd of cycle
Evaporator temperature15 °F5 °F0 °F
Evaporator pressure R-12 (psig)17129
Evaporator pressure R-134a (psig)14106
Condenser temperature70 °F100 °F130 °F
Condenser pressure R-12 (psig)70116180
Condenser pressure R-134a (psig)71124198

Typical R-134a fridge with a freezer. About 5 to 10 psig on the low side and about 150 psig on the high side is a normal reading. A restriction pulls the low side into a vacuum and sends the head above 200 psig.

Typical 18 ft³ fridge-freezer by room temperature

Room tempCabinet tempRun timekWh per dayWatts
70 °F38 °F38%3.8390 ± 20
90 °F40 °F62%6.0395 ± 20
100 °F47 °F100%9.9395 ± 20

Many fridges run about one third of the time (for example 5 minutes on, 10 minutes off). Any unexpected change in cycling is worth checking.

Electrical checks on a fridge

Thermostat bench test

Filter-drier size for small systems

Drier sizeCompressor
2 in³1/8 hp
3 in³1/6 to 1/4 hp
6 in³1/4 to 1/2 hp
9 in³1/2 to 3/4 hp

Replace the drier whenever the circuit is opened. Never use liquid antifreeze-type driers. Desiccant holds about 16% of its weight (silica gel), 12% (activated alumina) or 16% (synthetic silicate).

Replacement capillary tube for room A/C (inside diameter × length)

CompressorR-410AR-22
1/8 hp0.28 in × 81 in0.28 in × 58 in
1/6 hp0.28 in × 78 in0.28 in × 86 in
1/5 hp0.31 in × 41 in0.31 in × 28 in
1/4 hp0.31 in × 101 in0.31 in × 72 in
1/3 hp0.40 in × 62 in0.40 in × 43 in
1/2 hp0.52 in × 42 in0.52 in × 109 in
3/4 hp0.52 in × 34 in0.64 in × 87 in
1 hp0.64 in × 94 in0.64 in × 65 in

Cut a capillary tube by filing a notch and snapping it. A tube cutter squeezes the inside. A replacement must match the diameter and length exactly.

Room and split A/C

Take it with you

All of these tables, plus the calculators, are in the HVACopedia app, offline.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.