Motor data

Speeds, efficiency, fuses, code letters, insulation and motor types.

Motor speed by poles

Poles60 Hz synchronous60 Hz full load50 Hz synchronous50 Hz full load
23600about 34503000about 2850
41800about 17501500about 1450
61200about 11501000about 950

RPM = 120 × Hz ÷ poles. Slip takes about 4 to 5% off at full load. A motor wound for one frequency should run only on that frequency.

Premium-efficiency minimums

Motor size (hp)2 pole4 pole6 pole
177.0%85.5%82.5%
1.584.0%86.5%86.5%
285.5%86.5%87.5%
385.5%89.5%88.5%
586.5%89.5%89.5%

Large motors reach about 97% efficient. Small motors are often only 50 to 60%.

Largest fuse for small motors

Motor size (hp)120 V240 V
1/64.4 A2.2 A
1/45.8 A2.9 A
1/37.2 A3.6 A
1/29.8 A4.9 A
3/413.8 A6.9 A
116.0 A8.0 A
1 1/220.0 A10.0 A

Fast-acting fuses suit blowers. Compressors and other high-starting-current motors need time-delay (dual-element) fuses, which ride through about 10 seconds of overload.

Insulation class and winding temperature

ClassHighest winding temperature
A221 °F (105 °C)
B266 °F (130 °C)
F311 °F (155 °C)
H356 °F (180 °C)

Locked-rotor code letters

LetterkVA per hp
A0 to 3.14
B3.15 to 3.54
C3.55 to 3.99
D4.0 to 4.49
E4.5 to 4.99
F5.0 to 5.59
G5.6 to 6.29
H6.3 to 7.09
J7.1 to 7.99
K8.0 to 8.99
L9.0 to 9.99
M10.0 to 11.19
N11.2 to 12.49
P12.5 to 13.99
R14.0 to 15.99
S16.0 to 17.99
T18.0 to 19.99
U20.0 to 22.39
V22.4 and up

kVA per horsepower with the rotor locked. Locked-rotor amps are usually 2 to 6 times full-load amps.

Single-phase motor types

TypeHow it startsTypical use
Split-phaseStart winding dropped out at about 75% speedFans and small units up to 1/3 hp; cap-tube systems whose pressures equalize
CSIRStart capacitor in series with the start winding, dropped out at about 75% speedHermetic refrigeration compressors up to 3 hp
CSCRStart capacitor (switched) plus a run capacitor that stays inLarge commercial hermetics and belt-drive blowers (1/6 hp and up)
PSCOne run capacitor, no switch. Low starting torqueMulti-speed blowers and fans; easy-start compressors with equalized pressures. Sensitive to low voltage
Shaded poleCopper bands on the poles, no start windingSmall fans, 1/100 to 1/6 hp
Three-phaseNo start winding or capacitor1 hp and up. Dual voltage motors have 9 leads: series for 480 V, parallel for 240 V
ECMBrushless DC motor with an electronic moduleBlowers and fans with soft start and variable speed

Temperature and nameplate rules

Take it with you

All of these tables, plus the calculators, are in the HVACopedia app, offline.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.