Comfort, humidity & air quality
MERV ratings, comfort ranges, dew points, recommended humidity, CO exposure.
MERV filter ratings
| MERV | Particle size | Catches | Typical use |
|---|---|---|---|
| 1 to 4 | over 10 µm | Pollen, dust mites, sanding dust, textile fibres | Window A/C, basic residential |
| 5 to 8 | 3 to 10 µm | Mould spores, hair spray, cement dust | Better residential, commercial |
| 9 to 12 | 1 to 3 µm | Lead dust, flour, vehicle exhaust, welding fumes | Superior residential, hospital labs |
| 13 to 16 | 0.3 to 1 µm | All bacteria, most tobacco smoke, copier toner | Hospitals, surgery, superior commercial |
MERV 12 to 13 is a good target for air quality. A HEPA filter removes 99.97% of 0.3 µm particles. Filters do not remove gases or odours: use activated charcoal or an oxidizing media.
Comfort ranges
| Season | Relative humidity | Comfortable temperature |
|---|---|---|
| Summer | 30% | 76 to 82 °F |
| Summer | 60% | 74 to 78 °F |
| Winter | 30% | 69 to 78 °F |
| Winter | 60% | 68 to 75 °F |
General comfort zone: 30 to 70% RH at 70 to 85 °F. For air quality aim for 40 to 60% RH and 72 to 76 °F. Indoor to outdoor summer difference of 10 to 15 °F is comfortable.
Recommended indoor humidity by outdoor temperature (indoor 72 °F)
| Outdoor temp | Indoor RH |
|---|---|
| −10 °F | 20% |
| 0 °F | 25% |
| 10 °F | 30% |
| 20 °F | 35% |
| 30 °F | 40% |
Go slightly higher if the house is cooler than 72 °F and lower if warmer. Mould grows above 50% and thrives at 70%. Windows fogging means the humidity is too high for the outdoor temperature.
Surface temperature where condensation starts
| Room RH | Room at 70 °F | Room at 80 °F |
|---|---|---|
| 100% | 70 °F | 80 °F |
| 90% | 67 °F | 77 °F |
| 80% | 64 °F | 73 °F |
| 70% | 60 °F | 69 °F |
| 60% | 56 °F | 65 °F |
| 50% | 51 °F | 60 °F |
| 40% | 45 °F | 54 °F |
| 30% | 37 °F | 46 °F |
| 20% | 28 °F | 35 °F |
Use it to answer "will this window or duct sweat?". Anything colder than the number in the table will collect condensation.
Carbon monoxide and other exposure
| Level | Effect |
|---|---|
| 0 ppm | Target indoors |
| 200 to 400 ppm | Slight headache |
| 1000 to 2000 ppm | Palpitations within 30 minutes; staggering within 1.5 hours; confusion, nausea and headache after 2 hours |
| 2000 to 2500 ppm | Unconscious within 30 minutes |
| 2500 ppm and over | Collapse and death before warning symptoms |
| CO₂ up to about 700 ppm | Good ventilation. A higher number marks poor ventilation |
| Ozone 0.1 ppm | Maximum for 8 hours. Continuous occupancy: 0.01 ppm |
Air quality problems and fixes
| Problem | Fix |
|---|---|
| VOCs and odours | HRV or ERV, air purifier, remove the source |
| Particles and bio-aerosols | MERV 13 or better filter, UV light at the coil |
| Humidity | Keep 25 to 55%: humidifier or dehumidifier |
| Temperature | Better thermostat and airflow, 68 to 81 °F |
| CO₂ | HRV or ERV, fresh air, new filters |
| CO | Repair or vent the appliance, no running vehicle in an attached garage, CO alarm |
About 20% or more of occupants with symptoms that clear when they leave is a sign of a sick building. Use an HRV in cold climates and an ERV where moisture control matters. Some ionizers make ozone: do not use ozone-generating cleaners.
Other numbers
- A water heater set at 140 °F or higher helps control Legionella in a single-family home.
- UV germicidal lamps are 254 nm. Clean quarterly, replace yearly. An access door on a UV lamp should have a shut-off interlock. Never look at a lit lamp.
- Electronic air cleaner cell: about 9,000 V DC. Clean cells and prefilter every 2 to 3 months, dry completely before refitting.
- Degree days = 65 °F minus the average of the daily high and low (cooling degree days are the opposite).
Take it with you
All of these tables, plus the calculators, are in the HVACopedia app, offline.
Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.