Heat pump data

Defrost, balance point, reversing valve, charging conditions and installation.

Key numbers

ItemValue
Defrost timer intervals30, 60 or 90 minutes (a jumper on the board)
Defrost startswhen the coil sensor is below about 26 °F
Defrost endson coil temperature, or after a maximum of about 10 minutes
Outdoor fan during defrostoff
Auxiliary heat during defroston
Check the chargecooling above 70 °F outdoors, heating below 40 °F outdoors
Outdoor unit on risers8 to 18 in above the snow line
Supply air temperaturecooler than a furnace; warn new owners

Reversing valve

Good to know

Take it with you

All of these tables, plus the calculators, are in the HVACopedia app, offline.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.