Gas appliance data

Combustion targets, flames, gas properties, furnace classes and venting.

Combustion targets (natural gas and propane)

ReadingNatural gasPropane
CO₂about 7.6%about 8.9%
Ultimate (undiluted) CO₂11.9%13.9%
Oxygen6 to 9% (about 7.5% ideal)6 to 9% (about 7.5% ideal)
Manifold pressure3.5 in. WC10.5 in. WC
Carbon monoxideunder 50 ppm normal; absolute limit 400 ppm air-freesame

Low CO₂, high oxygen and CO: too much excess air or gas pressure too low. High CO₂, low oxygen and CO: not enough air or gas pressure too high. Check the manifold pressure before changing the air.

Stack temperature

Combustion efficiency of gas (percent)

Excess airO₂200 °F300 °F400 °F500 °F600 °F
9.5%2%85.483.180.878.476.0
15%3%85.282.880.477.975.4
28%5%84.782.179.576.774.0
45%7%84.181.278.275.272.1
82%10%82.879.375.671.968.2

By flue oxygen and net stack temperature. Interpolate between values.

Flame conditions

FlameCauseWhat to check
Soft blue, no tipping, no liftingGood combustionNothing
YellowNot enough primary airReset the primary air shutter, look for blockage, dust or a bad burner
LiftingGas speed faster than the flame speedReduce gas pressure or primary air
Popping (flashback at shut-off)Flame travels back into the burnerRaise gas pressure, reduce primary air or orifice size, check valve and burners
Floating (very dangerous, makes CO)Incomplete combustionCheck gas flow, flue, burners, secondary air and primary air
Rollout (very dangerous)Blocked flue, poor draft, not enough air, overfiringSame checks as floating; find the cause before resetting the rollout switch

Orange flecks are usually dust burning, not an air problem.

Gas properties

ItemNatural gasPropane
Heating value1000 to 1100 BTU/ft³2500 BTU/ft³
Air needed for burning (theory)10 ft³ per ft³24 ft³ per ft³
Air with about 50% excessabout 15 ft³ per ft³about 35 ft³ per ft³
Ignition temperature1100 to 1200 °F920 to 1020 °F
Flammable range (percent gas in air)4.0 to 14.0%2.4 to 9.5%
Weight compared to airLighter, risesHeavier, pools in low spots

Butane: 3200 BTU/ft³, boils at 32 °F. 28 in. WC is about 1 psi. LP is much heavier than air: gas from a failed pilot collects in low places, so ventilate basements and crawlspaces.

Furnace classes

ClassAFUEFeatures
Low efficiency68 to 72%Natural draft, standing pilot
Mid efficiency79 to 83%Spark or hot-surface ignition, induced draft, 3 in. flue, Class B vent or approved liner
High efficiency (condensing)90 to 97%Secondary heat exchanger, PVC vent

Condensate forms in furnaces above about 83% AFUE. Excess air: 20 to 50% on older furnaces, as low as 10% on high-efficiency ones.

Venting categories

CategoryVent pressureCondensingVent type
INegativeNoClass B vent (most mid-efficiency furnaces); flue gas 140 °F or more
IINegativeYesSpecial vent per manufacturer
IIIPositiveNoStainless steel
IVPositiveYesPVC; flue under 140 °F

More gas furnace numbers

Take it with you

All of these tables, plus the calculators, are in the HVACopedia app, offline.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.