Duct & airflow data
Air speeds, duct metal gauges, pressure drops, air density and leakage limits.
Maximum air speed in ducts (fpm)
| Building | Main supply | Main return | Branch supply | Branch return |
|---|---|---|---|---|
| Homes and apartments | 1000 | 800 | 600 | 600 |
| Auditoriums and theatres | 1300 | 1100 | 1000 | 800 |
| Offices, banks, libraries, meeting rooms, restaurants, shops | 2000 | 1500 | 1600 | 1200 |
| Hospital and hotel rooms | 1500 | 1300 | 1200 | 1000 |
| Industrial | 3000 | 1800 | 2200 | 1500 |
In a residential duct, over 700 fpm is often noisy. Over 500 fpm at a register is felt as a draft. A draft is also anything over about 15 to 20 fpm in an occupied space.
Typical pressure drops (in. WC)
| Device | Drop |
|---|---|
| Filter | 0.08 to 0.15 |
| Evaporator coil | 0.10 to 0.30 |
| Air cleaner | about 0.20 |
| Damper | about 0.03 |
| Register, diffuser or grille | about 0.03 |
Available static pressure = blower external static pressure − device drops. A residential system should not exceed 0.5 in. WC total (supply static plus return static). Replace a filter when its drop is more than 25% of the blower's pressure rise.
Round duct metal thickness (gauge)
| Diameter | Commercial | Residential |
|---|---|---|
| 12 in or less | 26 | 30 |
| 13 to 18 in | 24 | 28 |
| 19 to 28 in | 22 | – |
| 27 to 36 in | 20 | – |
| 35 to 52 in | 18 | – |
Rectangular duct metal thickness (by wide side)
| Wide side | Commercial galvanized | Aluminium (in) | Residential galvanized |
|---|---|---|---|
| 12 in or less | 26 | 0.020 | 28 |
| 13 to 23 in | 24 | 0.025 | 26 |
| 24 to 30 in | 24 | 0.025 | 24 |
| 31 to 42 in | 22 | 0.032 | – |
| 43 to 54 in | 22 | 0.032 | – |
| 55 to 84 in | 20 | 0.040 | – |
| 85 in and over | 18 | 0.050 | – |
Aspect ratio
| Class | Ratio | Wide side | Perimeter |
|---|---|---|---|
| 1 | 1 : 1 | 6 to 18 in | 24 to 72 in |
| 2 | 2 : 1 | 12 to 24 in | 36 to 72 in |
| 3 | 3 : 1 | 26 to 40 in | 70 to 106 in |
| 4 | 4 : 1 | 24 to 88 in | 60 to 220 in |
| 5 | 5 : 1 | 48 to 90 in | 116 to 216 in |
| 6 | 6 : 1 | 90 to 144 in | 210 to 336 in |
A square duct needs the least metal. A 20 × 5 duct has the same area as a 10 × 10 but uses 25% more metal.
Air density
| Temp (°F) | Dry air (lb/ft³) | Dry air (ft³/lb) |
|---|---|---|
| 0 | 0.08635 | 11.58 |
| 50 | 0.07786 | 12.84 |
| 70 | 0.07492 | 13.35 |
| 100 | 0.0709 | 14.10 |
| 120 | 0.0685 | 14.60 |
| 150 | 0.0652 | 15.30 |
| 200 | 0.0600 | 16.70 |
Standard air: 0.075 lb/ft³. Heat in air: 0.24 BTU/lb·°F. Sensible heat BTU/h = 1.08 × cfm × temperature difference.
Rules of thumb
- Cooling airflow: about 400 cfm per ton. Cooling needs 30 to 50% more air than heating, so a blower may need a different tap or pulley for each.
- Branches go into the side of a plenum, never the end, because an end duct hogs the air.
- Reducing transitions: 1 inch of change per 4 inches of length. Enlarging: 1 inch per 4 to 7 inches.
- A return grille blocks about 30% of its face. Allow for it.
- Seal ducts with mastic (1 inch each side of the joint, with mesh for gaps wider than 1/4 inch), never duct tape.
- Return grilles belong in the stagnant zone: near the floor for heating, near the ceiling for cooling, and far from supplies.
- Duct leakage: a common limit is 4 cfm at 25 Pa per 100 ft² of conditioned floor area. Check the code that applies to your job.
- Blower-door limit often quoted: 3 ACH at 50 Pa. Check local code.
- Pitot tube: velocity (fpm) = 4005 × √(velocity pressure in in. WC) for standard air. Measure at least 10 duct diameters downstream of any fitting and average a traverse.
- Swinging-vane anemometers are calibrated for 68 °F. At other duct temperatures, corrected speed = reading × (460 + duct °F) ÷ 528.
Typical air changes per hour
| Space | Heating | Cooling |
|---|---|---|
| Homes | 3 to 6 | 6 to 9 |
| Offices | 5 to 8 | 6 to 12 |
| Public assembly spaces | 5 to 10 | 6 to 12 |
Minimum for a home in heating is about 3 ACH. Outdoor air per person: about 15 cfm. Time for one change (min) = volume ÷ cfm.
Take it with you
All of these tables, plus the calculators, are in the HVACopedia app, offline.
Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.