Duct & airflow data

Air speeds, duct metal gauges, pressure drops, air density and leakage limits.

Maximum air speed in ducts (fpm)

BuildingMain supplyMain returnBranch supplyBranch return
Homes and apartments1000800600600
Auditoriums and theatres130011001000800
Offices, banks, libraries, meeting rooms, restaurants, shops2000150016001200
Hospital and hotel rooms1500130012001000
Industrial3000180022001500

In a residential duct, over 700 fpm is often noisy. Over 500 fpm at a register is felt as a draft. A draft is also anything over about 15 to 20 fpm in an occupied space.

Typical pressure drops (in. WC)

DeviceDrop
Filter0.08 to 0.15
Evaporator coil0.10 to 0.30
Air cleanerabout 0.20
Damperabout 0.03
Register, diffuser or grilleabout 0.03

Available static pressure = blower external static pressure − device drops. A residential system should not exceed 0.5 in. WC total (supply static plus return static). Replace a filter when its drop is more than 25% of the blower's pressure rise.

Round duct metal thickness (gauge)

DiameterCommercialResidential
12 in or less2630
13 to 18 in2428
19 to 28 in22–
27 to 36 in20–
35 to 52 in18–

Rectangular duct metal thickness (by wide side)

Wide sideCommercial galvanizedAluminium (in)Residential galvanized
12 in or less260.02028
13 to 23 in240.02526
24 to 30 in240.02524
31 to 42 in220.032–
43 to 54 in220.032–
55 to 84 in200.040–
85 in and over180.050–

Aspect ratio

ClassRatioWide sidePerimeter
11 : 16 to 18 in24 to 72 in
22 : 112 to 24 in36 to 72 in
33 : 126 to 40 in70 to 106 in
44 : 124 to 88 in60 to 220 in
55 : 148 to 90 in116 to 216 in
66 : 190 to 144 in210 to 336 in

A square duct needs the least metal. A 20 × 5 duct has the same area as a 10 × 10 but uses 25% more metal.

Air density

Temp (°F)Dry air (lb/ft³)Dry air (ft³/lb)
00.0863511.58
500.0778612.84
700.0749213.35
1000.070914.10
1200.068514.60
1500.065215.30
2000.060016.70

Standard air: 0.075 lb/ft³. Heat in air: 0.24 BTU/lb·°F. Sensible heat BTU/h = 1.08 × cfm × temperature difference.

Rules of thumb

Typical air changes per hour

SpaceHeatingCooling
Homes3 to 66 to 9
Offices5 to 86 to 12
Public assembly spaces5 to 106 to 12

Minimum for a home in heating is about 3 ACH. Outdoor air per person: about 15 cfm. Time for one change (min) = volume ÷ cfm.

Take it with you

All of these tables, plus the calculators, are in the HVACopedia app, offline.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.