Pressure & temperature controls

Cut-out settings, adjustment directions, differentials and control signals.

Low-pressure control settings (psig, cut-out / cut-in)

ApplicationEvaporator tempTemp differenceR-22R-134aR-404AR-507
Beverage, floral, produce cooler35 to 38 °F15 °F41 / 6617 / 3353 / 8256 / 86
Smoked meat, reach-in meat, service deli, seafood32 to 35 °F15 °F38 / 6215 / 3049 / 7752 / 81
Multi-deck fresh meat26 to 29 °F15 °F32 / 5411 / 2542 / 6844 / 71
Frozen glass door, frozen walk-in−10 to 0 °F10 °F9 / 24–15 / 3316 / 35
Ice cream, open frozen food−30 to −20 °F10 °F0 / 10–3 / 164 / 18

A starting point for commercial refrigeration. Cut-out is about the saturation pressure at 10 °F below the evaporator surface temperature you want. Cut-in is about the saturation pressure at the highest evaporator temperature you accept.

High-pressure safety cut-out (psig)

RefrigerantCut-out
R-12150 to 160
R-22260 to 270
R-500190 to 200
R-502280 to 290

Rule of thumb: set the high-pressure safety about 20% above the normal head pressure. For newer refrigerants use the manufacturer's setting. A high-pressure control is a safety, not an operating control.

Typical pressure range between cut-in and cut-out

RefrigerantDifference (psi)
R-2222
R-401A20
R-404A20
R-134a16

Adjusting a pressure control

Thermostat and evaporator reference

ItemValue
Room A/C thermostat cut-out56 to 60 °F
Room A/C thermostat cut-in77 to 80 °F
Room A/C differential3 to 8 °F
Air temperature drop across an evaporator (room A/C)about 5 °F between inlet and outlet
Central A/C temperature split16 to 20 °F
Freezestat opensabout 33 °F above the evaporator (most close again on a 5 °F rise)
Best evaporator coil temperature34 to 36 °F
Heating thermostat differential0.5 to 2 °F
Heat anticipator current range0.15 to 1.0 A
Multistage thermostat, second stageCloses when the room is more than about 3 °F from setpoint (adjustable)

Control signals

Damper position0 to 10 V signal
Fully open0 V
25% closed2.5 V
50% closed5 V
75% closed7.5 V
Fully closed10 V

Building controls use 0 to 10 V DC or 4 to 20 mA on light twisted-pair wire. Electronic sensors run on 5 to 15 V. A thermopile gives up to 750 mV.

Take it with you

All of these tables, plus the calculators, are in the HVACopedia app, offline.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.