Compressor electrical values

Winding resistance, power, megger readings and replacement rules.

Typical single-phase winding resistance

Compressor size (hp)C to R (Ω)C to S (Ω)R to S (Ω)
1/24.718.623.3
3/43.311.915.2
12.511.013.5
1 1/21.98.410.3
22.16.48.5

Approximate values. Always compare with the compressor data sheet. C = common, R = run, S = start.

Hermetic compressor power, 120 V single phase

Size (hp)Running watts at 70 °FRunning watts at 110 °FStarting watts
1/1666100375
1/9117160740
1/8108163743
1/7160218970
1/42353201250

On a wattmeter a good start circuit shows a short pause at the combined start and run watts before dropping to the run watts.

Megohmmeter readings (winding to shell)

ReadingConditionWhat to do
Over 100 MΩExcellentNothing
60 to 100 MΩSome insulation breakdown or moistureChange the filter-drier; clean the windings if you can reach them
40 to 60 MΩOverheated winding, dirty oil or moistureChange the filter-drier. A burnt smell in the oil means an overheated winding; no smell means dirty oil, so change it
20 to 40 MΩBadly contaminated oil, failure likely soonChange the oil and the driers. If the oil is burnt, check every motor, including the fans, for worn bearings

Test at 500 to 1000 V DC. Run the compressor at least an hour first so readings are comparable. Never megger a system that is under vacuum. Record the readings and watch the trend.

Relays and capacitors

Add-on start capacitor for a PSC compressor

Run capacitor (µF)Add-on start capacitor (µF)
2018
2518 or 25
3025
3525
4025 or 45
4545
5045

Use only with a start relay that drops the capacitor out once the compressor is running, and follow the manufacturer when there is a kit for the model.

Take it with you

All of these tables, plus the calculators, are in the HVACopedia app, offline.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.