Boiler & oil burner data

Boiler temperatures, expansion tanks, glycol, water limits and oil burner numbers.

Hot water boilers

ItemValue
Supply and return difference at the boiler (design)about 20 °F; much less points to circulation or air trouble
Conventional boiler return waterkeep above 140 °F to stop flue gas condensing (some tolerate down to 105 °F)
Operating range90 to 200 °F
Mixing valve settingsabout 140 °F return side, 160 °F supply side
Expansion tank air prechargeabout 12 psi. Check with a tire gauge with the makeup water isolated
Water pH7 to 10
50% propylene glycolprotects to about −30 °F but reduces heat output to about 90%
Condensing boilersabove 90% efficient; recover about 970 BTU for every pound of flue gas condensed
Steel pipe growthabout 3/4 in per 100 ft per 100 °F rise
Copper pipe growthabout 11/16 in per 100 ft per 100 °F rise

Boiler water limits (ppm)

SubstanceLimit
Sodium sulfite1.0
Sodium chloride10
Sodium phosphate25
Sodium sulfate25
Silica0.2
Total dissolved solids50

Boil-out: about 1 lb of trisodium phosphate per 50 gallons, circulate about 4 hours, drain, clean strainers, refill.

Tips and checks

Oil burner numbers

ItemValue
No. 2 oil heat content140,000 BTU per gallon
Pump pressure (standard)100 psi
Draft over the fire and in the flue−0.02 to −0.03 in. WC
CO₂8 to 12% (under 8% is incomplete combustion)
Stack temperature range300 to 900 °F
Electrode gap1/8 to 3/16 in
Electrode height above nozzle centre1/2 to 5/8 in
Ignition transformer10 to 14 kV (14 kV preferred)
Solid-state igniter14 to 20 kV at 20 kHz
Single-stage pump suction limit12 in. Hg
Two-stage pump suction limit17 in. Hg

Never raise the pump pressure to fix a problem and never fit a higher-capacity nozzle: that overfires the burner. A dull orange or red flame means not enough air. Take readings after the flue has stabilized, about 5 minutes.

Oil furnace efficiency by net stack temperature

Net stack (°F)Efficiency
100065 to 69%
80070 to 73%
60076 to 79%
40082 to 84%

Oil line and tank

ItemValue
Line, 50 to 100 ft3/8 in copper
Line, 200 to 300 ft1/2 in copper
Minimum supply / return3/8 in / 1/4 in inside diameter
Gravity tank to furnace (one-pipe)at least 7 ft away, less than 25 ft of elevation
Fuel pickup above tank bottom3 to 4 in
Tank vent, up to 660 gal1 1/4 in
Tank vent, 661 to 3000 gal1 1/2 in
Tank vent, 3001 to 10,000 gal2 in

Cold oil is thick: viscosity doubles at 0 °F. Blow oil lines out with nitrogen only, never compressed air or oxygen. Check all three filters: the line filter, the pump strainer and the nozzle strainer.

Take it with you

All of these tables, plus the calculators, are in the HVACopedia app, offline.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.