Viessmann · Boiler · Vitotronic 100, GC1 series

CM2 parts

5 replacement parts that fit the Viessmann CM2, with OEM part numbers, grouped by system.

Other

PartPart #QtySize / rating
Boiler coding card for Vitocrossal 200 CM2
Plug-in location X7
1041 7820 1451
Fixed high limit (STW)
Types STW 56.10525.570 (EGO) or EM-80-V-TK/b7-1 (Juchheim). Capillary 3600 mm, central fastening M10.
7820 0361Factory setting 120 °C / 248 °F
Adjustable high limit
Types TR 55.18029.020 (EGO) or EM-1-V-TK/b1 (Juchheim). Capillary 3600 mm.
7817 5311Factory setting 95 °C / 203 °F
TÜV button
Used to check the fixed high limit. See the description on page 86 of the manual.
7819 3141
Input module 0 to 10 V
Needs software version 7 of Vitocontrol-S, VD2/CT3 or later (display 1st digit 7 or higher, via scan 2). Used for external boiler or supply temperature control.
7134 56110 to 10 VDC input

Source: Vitotronic 100 GC1 installation and service instructions, p. 113 (pages 46, 113, 114). Part names are written by HVACopedia.

Part numbers are taken from the manufacturer’s published repair parts documents and are listed so you can identify the right part. Manufacturers replace and supersede numbers over time, so confirm the number with your distributor before you order, and use factory-authorized parts on equipment under warranty. Replacing gas, electrical and refrigerant parts is work for a licensed technician. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.