Viessmann · Water heater
Red LED Impressed current anode fault
What the control is telling you
Red LED on the impressed current anode control unit means a fault. The unit gives 5 short beeps in 3-second intervals, then a 5-minute break. This sequence repeats 3 times, followed by a 2-hour break, and then the whole sequence repeats.
Applies to: Impressed current anode control unit
Likely causes
- Short circuit
- No water in the DHW tank
- Anode cables not connected
- Faulty anode or electronic unit
Test and repair steps
- Isolate the system from power before inspecting, and check that it is no longer live.
- Confirm the DHW tank is filled with water.
- Check that the anode cable and spade connectors are connected correctly.
- Look for a short circuit in the anode wiring.
- Replace the anode or electronic unit if it is faulty.
Models that show this code
3 models in Vitocell 100-V
Other codes on the same units
- Green LED Impressed current anode normal operation
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocell 100-V CVWC installation, service and operating instructions, p. 18. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.